22-0375 rev1.1 Monitor ISM/xL™ Hardware Guide 29
• Press Save. The next address is the third Smart/Vigil module address. Enter the next consecutive address
number after the last. E.g. “
15283”.
• Program the same as the last 2 addresses but only enter “4” for 16 outputs. “0” for inputs.
• This will now supply 64 inputs and 80 outputs. For smaller Chubb Smart/Vigil systems, it is only necessary to
program the number of inputs/outputs required. All 3 addresses may not be needed and other module addresses
could occupy their places.
• Exit the module programming and then go back to module programming and the first Smart/Vigil module address.
This initializes the module.
• Press Save. The following screen supplies three programming options. HSC (NOT USED), PRN (printer),
SMR (Chubb Smart/Vigil Concentrators).
• Printer programming is the same as with a Printer module (discussed later in this manual). Please refer to
programming it with that module, to program it with the Smart module.
• Press the button below SMR.
Smart/Vigil Concentrators Programming
• The next screen displays programming for the first Smart/Vigil concentrator.
• The top line displays: Conc1 (concentrator 1), [enable conc1, with the cursor under this box (press LCD
keypad left or right arrow keys) press any key number to make the box a
to enable the conc.] T [is it
necessary to test a seismic connected to this concentrator (seismic concentrator, safe/vault concentrator), enter
if yes],
S [how many seismics require a test signal (seismic concentrator has 1 seismic, a safe/vault
concentrator can have 1 seismic configured as a safe or a maximum of 5 for a vault) make each box a
for each
seismic]. E.g. for a commercial concentrator there are no seismics. Only enable the conc. and do not enable any
test selections. Press
Save.
• Programming for the next conc. is displayed. Programming for all concentrators continue in the same way.
Programming Inputs/Outputs
• Programming inputs is the same as any inputs with e.g. Expander module.
• With the Smart/Vigil module occupying the first module location, inputs for it begin at 009. 001 – 008 being on the
ISM/AFx main panel.
• When programming outputs, they begin at 009. 001 – 004 (005 – 008 not existing) being on the ISM/AFx main
panel.
• It is very IMPORTANT to remember that the 9
th
output for any concentrator with seismics to test must be
programmed as “AREA ON” [bCAPL programmable output code: 01.10XX (XX = area #01 – 10)] to generate the
test.
• Use the following chart to compare Chubb Smart/Vigil inputs/outputs as they are converted to ISM/AFx.