NX-8V2 Control Panel Installation Instructions
Introduction
This is the NX-8V2-Control Panel Installation Instructions.
Installations should only be done by trained professionals. Use
this document to install the system with default settings that
comply with UL requirements.
To install the keypad, other peripherals, and sensors, refer to
the documentation for those devices.
P/N 466-2339 • REV B • 02MAR11
Installation
There are four slots for board insertions inside the metal
enclosure, two on the top and two on the bottom. These allow
the PC board to be positioned vertically (Figure 1 below).
W
hen you slide the board between the grooves of the slots,
make sure the terminal strip is toward the front opening
(toward you) to allow for the wire connections.
Note: Install the metal enclosure with the door opening from
the top to bottom.
Figure 1: Board installation
NetworX keypad maximum wire run
Table 1 below lists wire lengths for one keypad at the end of
the wire. When connecting more than one keypad to the end of
the wire, a higher gauge wire is required
Table 1: Maximum keypad wire run
Length in feet Wire gauge for NX-
8V2
Wire gauge for NX320-
E
250 24 22
500 20 18
1000 18 16
1500 16 14
2500 14 12
Terminal descriptions
Table 2 below describes the panel terminals.
Table 2: NX-8V2 terminals
Terminal Description
R1 House telephone ring (grey)..
R Telephone ring (red).
T Telephone tip (green).
T1 House telephone tip (brown).
AC AC input. Connect to a 16.5 V 40 or 50 VA Class ll UL
approved transformer.
EARTH Earth ground. Connect to a cold water pipe or a 6 to 10 ft.
driven rod.
Bell + and
Bell -
If used as a siren output (default), the speaker rating
should be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8, or
16 ohms. If voltage ouput is selected in location 37, this
output becomes voltage output, 12 VDC, 1 Amp maximum
load. Note: A 3.3 kohm resistor may be required across
the bell terminals when a 12 VDC siren is used. If no
resistor is used, you may experience voltage leakage into
the siren, which will cause these devices to output a small
signal.
KP Data Connect to the data terminal on the keypads and the
expanders. Maximum number of devices (keypads plus
expanders) is 32. See Maximum Wire Run table.
KP COM Connect to the common terminal on the keypads and the
expanders.
Vista de pagina 0
1 2 3 4 5 6 ... 10 11

Indice de contenidos

Pagina 1 - Installation

NX-8V2 Control Panel Installation Instructions Introduction This is the NX-8V2-Control Panel Installation Instructions. Installations should only be

Pagina 2 - Control panel programming

ANSI/SIA CP-01 requirements CP-01 feature descriptions and specifications are listed in Table 9 below. The following are requirements for compliance w

Pagina 3

NX-8V2 Control Panel Installation Instructions 11 CP-O1 feature description Feature description as shown in manual Program location Seg/opt Default

Pagina 4 - Location 0 - Phone 1

Terminal Description KP POS Connect to the POS terminal on the keypads and the expanders. Individually, this terminal is limited to 1 amp. Combined,

Pagina 5 - Zone type Description

Select the module to program Since all modules connected to the NX-8V2 are programmed through the keypad, the module you are programming should be the

Pagina 6

Location 0 - Phone 1 Location 0 has 20 segments of numerical data. Use this location to program phone 1. The default for each segment is 14. • To pro

Pagina 7

Segment 2 - Phone 1 backup control Program the backup control for phone 1. The default is 0. • Program a 0 in segment 2 to cause the NX-8V2 to make t

Pagina 8

Zone type Description Zone type Description 2. 24-hour audible. This zone creates an instant yelping siren alarm regardless of the armed state of th

Pagina 9 - Regulatory information

UL294 Access control system units UL365 Police station connected burglar alarms UL609, CAN/ULC-S303-M91 Mercantile, police station connect with basic

Pagina 10 - ANSI/SIA CP-01 requirements

protected area, is acceptable, provided it is rated for outside service and alarm conditions are transmitted to: a) The dispatch location of the law e

Pagina 11

NX-8V2 Control Panel Installation Instructions 9 • The DACT shall be enabled for all commercial burglary applications. UL requires that an alarm pan