Interlogix Concord 4 REV J Installation Manual Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 153
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
Chapter 2: Installation
6 Concord 4 Installation Manual
Installation overview
Before starting the installation, plan your system layout and programming using
the worksheets provided in Appendix A System planning sheetson page 117.
Note: Class 2, Class 3, and power-limited fire alarm circuits must be installed
using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical
Code ANSI/NFPA 70 or Class 2, Class 3, and power-limited fire alarm circuit
conductors must be installed as Class 1 or higher circuits.
Note: Class 2, Class 3, and power-limited burglar alarm circuits must be installed
using CL2, CL2R, CL2P, or substituting cable permitted by ANSI/NFPA 70. Wire
that extends beyond the cable jacket must be separated from all other
conductors by a minimum of 0.25 in. or by a nonconductive barrier.
Use the following installation guidelines:
Centrally locate the panel with relation to detection devices whenever
possible, to help reduce wire run lengths and labor.
Locate the panel where the temperature will not exceed 120°F (49°C) or fall
below 32°F (0°C).
Avoid running wires parallel with electrical wiring or fixtures such as
fluorescent lighting, to prevent wire runs from picking up electrical noise.
Mount the panel at a comfortable working height (about 45 to 55 in. from the
floor to the bottom of the panel, as shown in Figure 1 on page 7).
Leave space to the left and right of the panel for wiring, phone jack, and
mounting optional modules. Allow at least 9 in. (23 cm) above the panel
cabinet for antennas. Allow at least 24 in. (62 cm) in front of the panel to open
the panel door.
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 152 153

Comentarios a estos manuales

Sin comentarios