
Appendix A
86 Concord Express Installation Instructions
SuperBus 2000 Devices (4 maximum)
SuperBus 2000
2x16 LCD
Alphanumeric
Touchpad
SuperBus 2000
Fixed Display
Touchpad
SuperBus 2000
2x20 LCD
Alphanumeric
Touchpad
SuperBus 2000
2x20 VFD
Alphanumeric
Touchpad
SuperBus 2000
Hardwire Input
Module
4 Input/2 Output
SnapCard
10 mA + 2.5 mA per
zone used
+ 7 mA per smoke
loop used
+ 34 mA per relay
used
8Z Hardwire Input
SnapCard
10 mA + 2.5 mA per
zone used
+ 7 mA per smoke
loop used
6 mA
+ 34 mA per relay
used
Total Standby Current Draw (must not exceed 90 mA
for UL systems)
Total Maximum Current Draw (must not exceed 750 mA)
Note: For UL listed systems, the difference between the standby current draw and the maximum
current draw of each device must be subtracted from the UL allowed alarm load of 650 mA (panel
terminal 7—OUT1/+12)
Comentarios a estos manuales