Regulatory information Contact information
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Complies with Part 68 FCC Rules.
ACTA (FCC) ID: GCQUSA-33408-AL-E
IC: 1175A-NXV2
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
For contact information, see www.utcfireandsecurity.com or
www.interlogix.com.
For technical support, Toll-free: 888.437.3287 in the US
including Alaska, Hawaii, Puerto Rico, and Canada. Outside
the tool-free area: Contact your dealer.
Copyright © 2011 UTC Fire & Security. All rights reserved.
ANSI/SIA CP-01 requirements
CP-01 feature descriptions and specifications are listed in Table 7. The following are requirements for compliance with ANSI/SIA
CP-01 standards.
Note: Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.
Minimum system requirements:
One control panel
Two keypads
Do not enable remote arming in SIA classified installations.
Off premise transmission must be in the SIA format.
Do not exceed 1 minute for the abort window and entry delay.
Note: A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station
Table 7. CP-01 feature descriptions and specifications
CP-01 feature description Feature description as
shown in manual
Progra
m
location
Seg/op
t
Default CP-01 required setting
Exit 1 delay 24 2 60 45 to 240 seconds Exit time
Exit 2 delay 24 4 60 45 to 240 seconds
Progress annunciation /
disable for silent exit <1>
Silent keypad option 93 2 All
annunciators
enabled
Allowed (individual keypads may be disabled)
Exit time restart (reexit) This feature is not programmable in the panel. Enabled
A
uto stay arm on unvacated
premises
Auto bypass 23 1/3 Enabled Enabled
Exit time and progress
annunciation/disable for
remote arm
This feature is not programmable in the panel. Exit time and
progress are always enabled.
Enabled (disabled for remote arming)
Exit 1 delay 24 1 30 30 to 240 seconds Entry delays <2>
Exit 2 delay 24 3 30 30 to 240 seconds
A
bort window - for
nonfire zones
Dialer delay 40 8 30 Enabled (may be disabled by zone/zone type,
but no cancel reports will be sent)
A
bort window time - for
nonfire zones <2>
Dialer delay 40 8 30 15 to 45 seconds
NX-6V2 Control Panel Installation Instructions 9