Configuring the System
24 TruPortal Software User Guide
1. Select System Administration > Devices.
2. Select the System Controller.
3. Click the General tab.
4. Select a Linked Camera if one is configured to monitor the System Controllers physical
location.
5. Click the Inputs tab.
6. For each general purpose auxiliary input that is connected:
a. Select Enabled.
b. Type a meaningful name.
c. Select the Type.
d. (Optional) Select Unlock All Doors if the input is from an alarm or emergency system.
e. (Optional) Select a Linked Camera if one is associated with the input source (for example,
a camera associated with a room motion detector).
7. Click the Outputs tab.
8. For each general purpose auxiliary output that is connected:
a. Select Enabled.
b. Type a meaningful name.
c. Select Active On/Off if the relay should be energized when the output is off, otherwise clear
the check box.
d. (Optional) Select a Linked Camera if one is associated with the output.
9. Click [Accept Changes].
10. Click [Reboot Controller] to restart the System Controller.
Configure Inputs and Outputs
Inputs and outputs are general purpose options that can configured to meet the needs of a site. An
input might be a signal from a motion detector, for example. An output is an electrical pulse from the
System Controller to some device.
Use the System Administration > Devices page to configure inputs and outputs. Inputs and outputs
can be monitored from the Monitoring > Inputs/Outputs page, and outputs can be activated manually
from that page. Outputs can also be controlled by action triggers.