Chapter 3: Reporting codes
NX-8V2 Control Panel Installation Manual 57
Table 11: Zone voltages ( 10%)
Two-wire smoke (680 ohm resistor)
Only low zone OK (3.74 kohm resistor)
Only high zone OK (6398 kohm resistor)
Both high and low zones OK
Normally open zones (such as four-wire smoke)
Use low zone resistor (3.74 kohm resistor).
Cannot use the corresponding high zone.
Specification
16.5 VAC 40 or 50 VA transformer
Auxiliary power
with 25 VA transformer
with 40 or 50 VA transformer
with NX-320E power supply
12 VDC regulated 500 mA
12 VDC regulated 1 A
12 VDC regulated 2 A plus control panel power
Loop resistance
Standard loop
Two-wire smokes
300 ohms max.
30 ohms max.
Two tone (temporal and yelp)
Selectable 50 mS or 500 mS