SIA system requirements are the same as those described for a
UL-listed basic system, plus if multiple annunciations are required,
use hardwired siren 13-046.
1RWHFor UL 1635 installations, entry delay plus dialer abort delay
must not exceed 60 seconds.
Table 8 below describes programming requirements to meet
ANSI-SIA CP-01.
7DEOH6,$VHWWLQJUHTXLUHPHQWV
)XQFWLRQ 'HIDXOW VHWWLQJ
5HTXLUHG VHWWLQJ
Entry delay 30 seconds 30 to 240 seconds
Exit delay 60 seconds 45 to 240 seconds
Dialer delay 30 seconds 15 to 45 seconds
Auto arm On On
Unvacated premises On On
Call waiting Off On if reporting to
central station and
customer has call
waiting service
Exit extension On On
Swinger shutdown On (one trip) On (one trip)
Fire alarm verify Off On
Duress/panic code Disabled Disabled
Cross zone Disabled Disabled for zones with
high probability of false
alarms
Table 9 below describes nonprogrammable (hard-coded) system
operation, as required to meet ANSI-SIA CP-01.
7DEOH1RQSURJUDPPDEOHV\VWHPRSHUDWLRQ
)XQFWLRQ 2SHUDWLRQ
Silent exit All annunciators enabled
Remote arming exit time and
progress annunciation
All annunciators enabled
Abort annunciation Enabled
Cancel report annunciation Enabled
Recent closing Enabled (2-minute window)
Exit error Enabled
Restoration of power Panel resumes operation in same
arming state and disregards alarm
signals from sensors for the first 60
seconds after power restoration
Cancel alarm Enter code only
&HQWUDOVWDWLR QUHSRUWLQJ
The panel has been tested with the following central station
receivers using SIA and Contact ID reporting formats:
1RWH Before beginning installation, installers must verify
compatibility with the following central station receivers.
• Radionics D6600 central station receiver
• Sur-Gard central station receiver with models SG-DRL2A and
SG-CPM2
• CS5000 digital alarm communicator receiver
8/&DQDGDOLVWHGLQVWDOODWLRQV
This section describes the requirements for CUL (UL Canada)
listed installations.
Canadian standards CSA certified accessories:
• Standard Class 2, 9 VAC, 3.34 A power transformer (model 22-
153-CN).
Residential burglary alarm system unit (ORD-C1023-1974): basic
system as described for UL 1023 listed installations plus:
• Hardwired magnetic contact (13-068 or 13-071) or wireless
learn mode door/window sensor (60-670)
• Siren timeout set to six minutes or more
Residential fire warning system control unit (ULC-S545-M89): basic
system as described for UL 985 listed installations plus:
• Wireless smoke sensor 60-848-02-95, TX-6010-01-1 learned
into sensor group 26
• Siren timeout set to six minutes or more
• For 24-hour backup, the total current draw for all connected
devices is limited to 250 mA (during normal standby
conditions) using a 1.2 AH battery.
)&&FRPSOLDQFH
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the FCC
rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful
interference to radio communications.
Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to
operate the equipment.
FCC Part 15 registration number: B4Z-910C-SIMON
IC: 1175C-910CSIMO
Part 68. This equipment complies with Part 68 of the FCC rules
and the requirements adopted by ACTA.
FCC registration number: US: B4ZAK02B55910
Canada: 1175C-910CSIXT
Ranger Equivalence 0.2B
Load Number 0.2
P/N 466-2398 • REV B • ISS 09JAN13 7 / 8