Appendix A:
74 Simon XT TableTop Control Panel Installation Manual
Specifications
Table 35: Simon XT TableTop Control Panel specifications
Requirement
Description
Power
9 VAC, 60 Hz, 25 VA transformer (minimum)
Rechargeable battery: 6.0 VDC, 1.2 Ah lead-acid. The battery will
last 24 hours with no AC and specified standby load of 250 mA.
Maximum battery charging current is 45 mA. With loss of AC
panel will continue to operate normally to a minimum of 5.1 VDC.
Radio frequency
319.5 MHz
Storage temperature range
-29 to140°F (-34 to 60°C)
Operating temperature range
32 to 120°F (0 to 49°C)
Maximum humidity
85% relative humidity, noncondensing
Auxliary power
Unregulated 5.3 to 12.3 VDC, with a maximum of 250 mA
Size (LxWxD)
7 x 5.75 x 2.125 in. (178 x 146 x 54 mm)
SIA system requirements
SIA system requirements are:
Control panel: backup battery 6 V 1.2 Ah (model # 34-025)
Standard class 2, 9 VAC, 3.34 A power transformer (model # 22-153)
Hardwired siren (model # 13-374)
Plus if multiple annunciation is required, use hardwired siren part no.13-046.
SIA setting requirements
Table 36 below describes programming requirements to meet ANSI-SIA CP-01
(see System programming on page 37).
Call waiting services should be disabled to prevent interrupting panel
communication to the central monitoring station
Table 36: SIA setting requirements
Function
Programming page
reference
Default setting
Required setting
Entry delay
Table 18 on page 48
30 seconds
30 to 240 seconds
Exit delay
Table 18 on page 48
60 seconds
45 to 240 seconds
Dialer delay
Table 13 on page 41
30 seconds
15 to 45 seconds